How VFD bearing damage develops
From a real investigation · 53 seconds
How a VFD destroys a motor bearing
Simplified for clarity; not to scale. Figures in chapters 6 and 7 are from the sanitized case study CS-01. The animated meter in chapter 3 is illustrative.
Read the full case studySelect mitigation for the current path
Common-mode voltage is the average of the three phase voltages relative to a reference such as the DC-link midpoint or ground. In a balanced sinusoidal system their sum may be zero; a PWM inverter's switching states can produce a nonzero, changing common-mode voltage. High-frequency currents then follow the installation's capacitive and conductive return paths. Capacitive discharge, circulating bearing currents and shaft-grounding currents need not call for the same remedy.
Differential-mode voltage is measured between phases. Fast voltage edges and cable reflections can stress motor insulation. A dV/dt filter or output reactor selected for that stress is not automatically a common-mode bearing-current solution. Evaluate the actual filter design and drive/motor/cable combination. High-frequency bonding and correctly terminated shielding manage return paths; shaft grounding provides a bypass where appropriate; insulated bearings interrupt particular loops and may redirect current elsewhere. Follow OEM guidance and verify the resulting path, including driven equipment.
The investigator confirmed the reported 21–34 V shaft-voltage range was peak-to-peak, not RMS. It is an observation from the case, not a universal bearing-damage threshold. Waveform records, reference point, probe method and bandwidth, speed, load and lubricant-film conditions affect interpretation. This animation illustrates a mechanism and recommended options; it does not show verified post-remediation performance.
Primary OEM reference: ABB Technical guide No. 5: Bearing currents in modern AC drive systems, chapters on current mechanisms and prevention. Have a qualified person assess the installation before selecting mitigation.
Read the explanation
A variable frequency drive feeds an AC motor through a long cable. The motor is rated "inverter duty." Nothing looks wrong.
PWM output is a train of fast voltage steps. The switching states can produce a nonzero common-mode voltage, so the motor sees a stepped common-mode voltage.
Stray capacitance between the stator windings and the rotor couples that common-mode voltage onto the rotor. The shaft floats at tens of volts, and the easiest way out is through the bearings.
The grease film insulates, so the voltage builds until the film breaks down. The discharge melts a microscopic pit in the race. At PWM switching rates this repeats millions of times.
Pitting turns the race a dull gray (frosting). Over time the balls' rhythm cuts a washboard pattern: fluting. The grease turns black. This is the race from the investigation.
No direct ground bond from drive to motor. Unshielded runs over 100–140 ft. Little drive output filtering. Almost no shaft grounding. The failures had been written off as "just how it is here."
Choose mitigation for the measured current path with the drive and motor OEM. High-frequency bonding, correctly terminated shielding, common-mode filtering, shaft grounding and bearing insulation have different roles; they are not interchangeable. Implementation and post-mitigation readings were not verified in this case.